Name Spec Size
 DC Inverter light commercial air conditioner  Ceiling cassette,Universal,Duct type  18KBTU-24KBTU-36KBTU-45KBTU-60KBTU
DESCRIPTION: MSN Chat     Send direct message to us 

*DC Inverter type is available for 18KBTU,24KBTU,36KBTU. Including DC inverter ceiling cassette type, floor ceiling console type, duct type air conditioner.

*Advantage of our DC inverter air conditioner

1. Phone call remote control enable simple unit operation with a simple phone call.
2. Full range capacity 18KBTU-60KBTU for different room size;
3. Operation under ambient temp from -20  to 53 centigrade;
4. Universal indoor PCB of all model for service convenience;
5. Japanese DC inverter high technology application;
6. High efficiency and energy saving;
7. Fast cooling and heating to achieve the setting temperature;
8. Auto restart function optional.
9. Low noise and low current start with wide range voltage(160V~260V);
10.Stable room temperature control to avoid sudden temperature change;
11.Electric expansion valve to ensure the perfect performance in various condition;
12.Fuzzy logic control for outdoor fan motor speed and frequency to keep durable running in extra 13.working condition;
14.Automatic self-diagnosis system for easy maintenance;
15.Intelligent failure protection function including over current, over or less voltage, over-16.heating, running blocked  to keep safely and durable operation.

Technical Data for DC Inverter Duct Type Air Conditioner:

Technical Data 18K 24K 36K
Cooling Capacity W 3,100 5,400 6,300 3,500 7,000 8,000 5,000 9,600 10,500
Heating Capacity W 3,200 5,900 6,800 3,600 7,500 8,400 5,200 10,200 11,200
Power Input (Cooling) W 1,550 2,320 3,150
Power Input (Heating) W 1,630 2,200 2,950
Voltage 230/1/50 230/1/50 230/1/50
EER W/W 3.48 3.02 3.05
Energy Class (Cooling) A B B
COP  W/W 3.62 3.41 3.46
Energy Class (Heating) A B B
Indoor Unit
Static Pressure Pa 40 50 60
Airflow m3/h 810/750/680/630 1100/1020/930/840 1690/1580/1450/1330
Sound Level dB(A) 39/37/35/33 40/38/36/34 43/41/39/36
Dimensions (WxHxD) mm 780x240x560 780x240x560 932x285x662
Net Weight Kgs 31 34 41
Outdoor Unit
Dimensions (WxHxD) mm 850x580x290 840x680x310 875x850x310
Sound Level dB(A) 51 52 56
Compressor Type Rotativo/Rotary
Net Weight Kgs 43 55 70
ø Liquid Pipe Inch 1/4 3/8 3/8
ø Gas Pipe Inch 1/2 5/8 5/8
Max. Piping Lenght m 25 50 50
Max. Height Diff. m 15 30 30

Technical Data for DC Inverter Ceiling Cassette Type Air Conditioner:

Model 18K 24K 36K
Capacity Cooling Kcal/h 4.730 (2.720-5.520) 6.320 (3.160-7.225) 8.085 (4.215-8.840)
W 5.500 (3.160-6.420) 7.350 (3.675-8.400) 9.400 (4.900-10.280)
Heating Kcal/h 5.330 (2.890-6.150) 7.050 (3.390-7.910) 8.600 (4.390-9.460)
W 6.200 (3.360-7.150) 8.200 (3.940-9.200) 10.000 (5.100-11.000)
Power Input Cooling W 1,570 2,400 3,020
Heating W 1,730 2,220 2,720
Cooling/Heating Amp 7,6 / 8,4 11,4 / 10,6 14,2 / 12,8
Voltage   230/1/50
EER W/W 3.50 3.06 3.11
Energy Class (Cooling)   A B B
COP    W/W 3.58 3.69 3.67
Energy Class (Heating)     A A A
   

Indoor Unit

Dimensions Body (WxHxD)   mm 570 x 250 x 570 840 x 240 x 840
Dimensions Grille (WxHxD)   650 x 30 x 650 950 x 40 x 950
Airflow (H/M/L)   m3/h 850 / 750 / 560 1020 / 880 / 730
Sound Level (H/M/L)   dB(A) 40 / 36 / 33 41 / 37 / 34
Net Weight (Body/Grille)   Kg 21 / 3 36 / 6
   

Outdoor Unit

Dimensions (WxHxD)   mm 850x580x290 840x680x310 875x850x310
Sound Level (H/M/L)   dB(A) 51 52 56
Net Weight     Kg 43 55 70
ø Liquid Pipe   Inch 1/4 3/8 3/8
ø Gas Pipe   Inch 1/2 5/8 5/8
Max. Piping Lenght   m 25 50 50
Max. Height Diff.   m 15 30 30
Compressor Type   Rotary
Refrigerant Charge Kg 1.60 2.00 2.50

[Return] [Top]  
CONTACT

China Heat Pump Manufactuer-Chengda Eco Tech 
Call me on SkypeCall me on Skype!

MSN Chat with me now
Send direct message to us
Tel:0086 20 39388753
Fax:0086 20 39388751
Email:info@china-heatpump.com
Website:www.china-heatpump.com

Address:Panyu Energy Hi-Tech Industrial Zone,Guangzhou, China Tel:86-020-39388753 Email:info@china-heatpump.com
MSN Chat With Me NowSend direct message to us
Copyright china heat pump|all in one heat pump|air heat pump |air source heat pump
Copyright 2002-2005 All rights reserved
Powered By :air to water heat pump